Forgot password?

HiPer Studio

HiPer MVHR
✓ Saved
✓ Saved
Project Details
Project Basics
Persons defaults to bed spaces if blank. Governing flow = max(persons×30, extract demand, 0.3 ACH).
Building Storeys
Inter-floor duct length = floor ceiling height + structural allowance per crossed floor level.
Duct Settings
MVHR Unit Selection
Select the unit you are designing for. The database is pre-loaded with PHI-certified units — import an updated list in Settings.
Loading units…
External Ducts & Grille
Supply Rooms
Airflow calculated from design total · enter name, area (m²) and duct run length
Extract Rooms
Twin duct auto-selected when normal flow >35 m³/h · enter name, area (m²) and duct run length
Airflow Design
Normal Airflow
m³/h
Low Speed (70%)
m³/h
Boost Speed (130%)
m³/h
PHI Governing Criteria
Occupancy
persons × 30
Extract Demand
sum of wet rooms
Min. 0.3 ACH
vol × 0.3
Unit Selection

System Balance

Total Supply
Total Extract (normal)
Difference
Status

Distribution Boxes

Supply manifold
Extract manifold
Total supply ducts
Total extract ducts
Est. system pressure
#RoomType Normal m³/hBoost m³/h Ductsm³/h / ductDuct status ACHTerminal m/sVelocity
Duct IDRoomFloorType Dia (mm)Run (m)Inter-floor (m)Bends Normal m³/hBoost m³/hBoost vel. m/sBoost ΔP (Pa)Status
#ItemModel / SpecQtyUnitNotes

Record measured airflows at commissioning. Supply and extract should each balance within ±5% of design. Adjust valves as required.

#RoomS / EDesign m³/hMeasured m³/hValve settingNotes

HiPer MVHR — User Manual

HiPer Studio · Passivhaus-aligned MVHR sizing for Australian high-performance homes

⚠️ View Disclaimer
Introduction

The HiPer Studio HiPer MVHR is a browser-based tool for sizing and documenting Mechanical Ventilation with Heat Recovery (MVHR) systems. It follows the Passivhaus Institute (PHI) three-criteria method, selects an appropriate unit, sizes individual duct runs, and produces a complete commissioning schedule.

All work auto-saves to your browser as named projects. No internet connection is required once the page is loaded.

ℹ️ Projects are stored in this browser only. Export the PDF as a backup before closing.
Navigation — Top Tabs
TabPurpose
📐 PlanUpload floor plan, draw building + rooms, place MVHR unit and grilles, auto-route ducts
🏗 ProjectEdit all design inputs: floor area, ceiling height, occupancy, duct settings, supply and extract rooms
📊 SummaryDesign airflow, unit selection, pressure loss and external grille summary — auto-updates as you draw
🏠 RoomsRoom-by-room schedule showing flow rates, duct count, velocity and status
🔩 DuctsIndividual duct run schedule with ID, length, velocity, pressure loss and status
📋 BOMBill of materials — all ComfoTube, fittings and terminals required
✅ CommissionCommissioning table ready to hand to the installer
⚠️ WarningsDesign warnings, code issues and informational notes
❓ HelpThis manual
Project Management
ControlAction
DropdownSwitch between saved projects. Current project auto-saves on switch.
✏️ RenameRename the current project.
+ New ProjectSave current work, then open a blank project with empty plan and rooms.
⧉ CopyDuplicate the current project including plan drawing and all inputs.
💾 SaveExplicit save — a ✓ Saved badge confirms. Auto-save also runs on every change (800ms debounce).
Plan Tool — Step-by-Step Workflow

The Plan tab is the primary input. Draw on your floor plan to populate the design automatically. Results update in the background as you work.

1
Upload your floor plan

Drag and drop a PDF or image (JPG/PNG) onto the upload area, or click to browse. PDFs use the first page.

2
Set the scale

Click 📏 Scale. Click two known points on the plan, then enter the real-world distance in metres. All subsequent measurements use this reference.

3
Draw the building outline

Click 🏗 Building. Click each corner of the external perimeter. Close by clicking back on the first point (snap ring appears) or double-click. Floor area auto-fills in Project.

4
Draw supply rooms

Click 🟢 Supply Room. Trace the polygon. A popup appears on completion — choose room type and name, then click Add Room. The room auto-populates the Project tab.

5
Draw extract rooms

Click 🟠 Extract Room. Same as supply rooms. Extract rooms (kitchens, bathrooms, wet areas) are shown in orange.

6
Mark V-Through zones

Click ↔ V-Through for hallways and open-plan corridors. These show on the plan but don't create duct runs — they allow air transfer between spaces.

7
Place the MVHR unit

Click 🔵 MVHR Unit, then click the plant room location. Duct routes are auto-drawn to every supply and extract room immediately.

8
Place intake and exhaust grilles

Click 🌬 Intake then click the external wall location. Click 💨 Exhaust for the exhaust outlet. Dashed external duct lines are drawn and lengths update automatically.

9
Re-route ducts

Click ⚡ Auto Route to regenerate all routes. Click any duct segment to insert a waypoint, then drag it to reroute. Waypoints snap to the unit and grilles.

10
Adjust outlets

Drag any outlet symbol within its room to the grille position. Click an outlet (without dragging) to toggle between ceiling-mounted and wall/bulkhead-mounted type.

Plan Toolbar Reference
ButtonModeInteraction
📏 ScaleTwo-pointClick 2 points → enter metres
🏗 BuildingPolygonClick corners → close to snap ring or double-click
🟢 Supply RoomPolygonClick corners → popup to name room
🟠 Extract RoomPolygonClick corners → popup to name room
↔ V-ThroughPolygonClick corners → popup to label zone
🔵 MVHR UnitSingle clickClick to place — auto-routes all ducts
🌬 IntakeSingle clickClick external wall — auto-draws external duct
💨 ExhaustSingle clickClick external wall — auto-draws external duct
⚡ Auto RouteActionRegenerates all duct routes
🗑 ClearActionConfirm prompt clears all plan markup
Outlet Symbols
SymbolMeaning
Blue circle + 4 outward arrowsCeiling-mounted supply grille
Red circle + 4 inward arrowsCeiling-mounted extract grille
Blue rectangle + 3 upward arrowsWall/bulkhead-mounted supply grille
Red rectangle + 3 downward arrowsWall/bulkhead-mounted extract grille
Calculation Methodology — PHI Three-Criteria Method

Design airflow is the maximum of three independently calculated values, per Passivhaus Institute protocol:

CriterionFormulaTypical governing scenario
Occupancy-basedPersons × 30 m³/hSmall, densely occupied homes
Extract demandSum of extract room defaults (kitchen 60, wet areas 40 each)Homes with multiple wet areas
0.3 ACH minimumFloor area × ceiling height × 0.3Large, lightly occupied homes
Duct Sizing

All ducts are DN90 (90mm) ComfoTube. Runs per room = ceil(normal flow ÷ 35 m³/h). At boost (1.3×), each DN90 carries up to 45.5 m³/h, keeping velocity below 2 m/s — the PHI limit for acceptable room noise.

StatusBoost velocityMeaning
Excellent< 1.0 m/sVery low velocity — may be oversized
Normal1.0–1.5 m/sComfortable operating range
High1.5–2.0 m/sAcceptable — approaching PHI limit
Critical> 2.0 m/sExceeds PHI limit — add a duct run
Design Tips
🍳 Kitchen extract ducts — PHI standard is 60 m³/h for kitchen extract. The tool splits this across two DN90 runs at 30 m³/h each. Do not combine into one — boost velocity would exceed 3 m/s.
🏠 Duplicate rooms — If the same room type appears multiple times, check whether a large open-plan area was drawn more than once. Delete duplicates and redraw as one polygon.
📏 External duct length — The plan measures straight-line distance. Add 10–15% for installed bends. Keep intake and exhaust runs under 5m where possible.
💨 Combi grille — Use the ComfoEdge combi grille where supply and exhaust share one wall penetration. Select DN125 (<3% recirculation) or DN160 (<5%). Do not use if the unit is more than 3m from the wall.
💾 Saving — Auto-save runs every 800ms. Use 💾 Save explicitly before switching browsers or computers. Projects are browser-local — export the PDF as a backup.
Default Airflow Weightings
Room TypeDefault m³/hType
Master Bedroom35Supply
Double Bedroom30Supply
Single Bedroom20Supply
Living Room40Supply
Rumpus Room30Supply
Dining Room25Supply
Study / Office20Supply
Kitchen60Extract
Bathroom / Ensuite40Extract
Laundry40Extract
WC20Extract
Pantry15Extract
Disclaimer & Limitations of Use

HiPer Studio Pty Ltd ("HiPer Studio") provides this software as a design assistance tool only. The outputs generated — including MVHR sizing calculations, unit selections, duct schedules, airflow schedules, pressure loss calculations, commissioning sheets, and design PDF reports — are indicative only and do not constitute professional engineering advice, certified design documentation, or a substitute for assessment by a licensed mechanical engineer.

By using this platform, you agree that:

  • All design outputs must be reviewed, verified, and signed off by a suitably qualified and licensed mechanical engineer or building services professional before use in any construction, installation, or compliance context.
  • HiPer Studio makes no warranty, express or implied, as to the accuracy, completeness, or fitness for purpose of any design output generated by this platform.
  • Compliance with applicable building codes, standards (including but not limited to NCC, AS 1668, Passivhaus requirements), and local regulations is the sole responsibility of the designer, engineer, and installing contractor.
  • HiPer Studio accepts no liability for any loss, damage, injury, or non-compliance arising directly or indirectly from reliance on outputs generated by this platform.
  • Site conditions, airtightness performance, occupant behaviour, and other factors affecting actual MVHR performance cannot be fully modelled by this tool and must be assessed independently.
  • Credits purchased are non-refundable once a design has been generated.

Use of this platform constitutes your acceptance of these terms in full. If you do not accept these terms, do not use this platform.

HiPer Studio HiPer MVHR — Always have designs reviewed by a qualified mechanical engineer before installation.

🏢 1 Storey
No scale set
📐
Upload a floor plan to get started
Accepts PDF or image files (PNG, JPG)
Calculation Defaults
These values follow the Passivhaus Institute (PHI) PHPP methodology. Adjust only if your project has specific requirements or a different standard applies.
PHI default: 30 m³/h
PHI default: 0.3 /h
Supply Room Defaults (m³/h)
Proportional weighting used to distribute total supply airflow across rooms.
Extract Room Defaults (m³/h)
Used directly as extract demand — sum governs total airflow if it exceeds occupancy criterion.
MVHR Unit Database
Import the PHI certified components update file (PHPP10_ventilation_*.xlsx) to update the unit database. Download the latest version from passivehouse.com.
Loading…
My Units (favourited for quick access)
Units you star in the Project tab appear here. Use this to keep only the equipment you actually supply.
Custom Units
Units you've added manually that aren't in the PHI database.